Always striving toward excellence, Dvolt has developed to be a market-driven and customer-oriented enterprise. We focus on strengthening the capabilities of scientific research and completing service businesses. We have set up a customer service department to better provide customers with prompt services including order tracking notice. rcd rccb We have professional employees who have years of experience in the industry. It is them that provides high-quality services for customers all over the world. If you have any questions about our new product rcd rccb or want to know more about our company, feel free to contact us. Our professionals would love to help you at any time.This Dvolt branded product has established its own excellent reputation in the market.
1.1Function
Control electric circuits.
Protect people against indirect contacts and additional protection against direct contacts.
Protect installations against fire hazard due to insulation faults.Residual current circuit breakers are used in housing, tertiary sector and industry.
1.2Selection
Detectable wave form
Ac class
Tripping is ensured for slowly increasing sinusoidal AC residual currents.
A class
Tripping is ensured for sinusoidal AC residual currents and for pulsed DC residual currents, whether applied suddenly or increasing slowly.
Tripping sensitivity
30mA - additional protection against direct contact.
100mA - co-ordinated with the earth system according to the formula lan <50/R,to provide protection against indirect contacts;
300mA - protection against indirect contacts,as well as fire harzard.
Tripping time
Instantaneous
It ensures instantaneous tripping (without time -delay).
Short time delay
lt ensures any tripping at least 10ms.
Selective
lt ensures total discrimination with a nonselective RCD placed downstream.